|Table of Contents|

The Arrangement of Ammonia Refrigeration Station
and Ventilation Simulation
(PDF)

《哈尔滨理工大学学报》[ISSN:1007-2683/CN:23-1404/N]

Issue:
2013年05期
Page:
76-81
Research Field:
测控技术与通信工程
Publishing date:

Info

Title:
The Arrangement of Ammonia Refrigeration Station
and Ventilation Simulation
Author(s):
JIANG Yong- qing YAN Yun- fei HU Jing- tao
School of Measurement- control Technology and Communications Engineering,Harbin University of Science and Technology
Keywords:
equipment arrangement accident ventilation ammonia leakage numerical simulation
PACS:
X928. 02
DOI:
-
Abstract:
Abstract: Based on the minimum exhaust accident research about making sure the ammonia concentration is un-
der IDLH( immediately dangerous to life or health concentration) when the refrigeration station’s ammonia compressor
is leaking by putting the equipment onto different places. At the same time,it discussed the wind path’s best height
and quantity of into- wind,on the refrigeration machine,to safe the staff working inside. Built up a refrigeration sta-
tion’s ammonia compressor leaking model by the way of Fluent numerical simulation. It tells the method of putting re-
frigeration station’s equipment and the quantity of exhausting air accident by dealing with data information. The result
is that the Refrigeration equipment should be put in the middle of the Station,the down- edge of the wind path s into-
wind should keep within 1 to 1. 5 m and no more than 2. 5 m. It also provides evident for installing of refrigeration sta-
tion s machine,selecting accident exhaust fan and the height of into- wind machine’s install.

References:

-

Memo

Memo:
-